Part Number Hot Search : 
00ETTT SK273 2SC25 3SK223 AT24C01 TFS244A IRF22 BAV70
Product Description
Full Text Search
 

To Download E5AR-TQQE3MWFLK Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 Programmable Digital Controller
E5AR-T
CSM_E5AR-T_DS_E_2_1
A new High-speed, High-precision Digital Controller that is Programmable!
* Create up to 32 programs with up to 256 segments total. * Coordinated operation for up to four channels with one Digital Controller. * 0.01C High resolution for Pt input. * High-speed sampling at 50 ms. * Settings easily made from a computer using the CX-Thermo. * RoHS compliance for world-wide application.
Refer to Safety Precautions for All E5@R Models.
Model Number Structure
Model Number Legend
E5AR-T@@@@@@@@-@@@
12345678 9
5. Communications Blank:None 3: RS-485 communications 6. Optional function Blank:None D: 4 event inputs M: 4 event inputs + 4 event inputs 7. Input 1 B: Universal-input and 2 event inputs F: Universal-input and FB W: Universal-input and universal-input 8. Input 2 Blank:None W: Universal-input and universal-input 9. Other FLK: CompoWay/F communications 1. Control method Blank:Standard or heating/cooling control P: Position proportional control 2. Output 1 R: NO relay output + NO relay output Q: Pulse output/current output + pulse output C: Current output + current output 3. Output 2 R: NO relay output + NO relay output Q: Pulse output/current output + pulse output C: Current output + current output 4. Auxiliary Outputs Blank:None 4: NO relay output + NO relay output E: 5 transistor outputs + 5 transistor outputs
Note: The above model number legend is intended as a functional description of models. Not all possible combinations of functions are available. Confirm model availability in Ordering Information when ordering.
Note: Be sure to read the precautions for correct use and other precautions in the following user's manual before using the Digital Controller. E5AR/ER Digital Controller User's Manual (Cat. No. Z182)
1
E5AR-T
Ordering Information
Digital Controllers
Programmable Digital Controllers
Size Control type Control mode Outputs (control/transfer) Optional functions Auxiliary outputs (SUB) Event inputs 2 Serial communications None E5AR-TQ4B E5AR-TC4B RS-485 E5AR-TQ43B-FLK (See note 2.) E5AR-TC43B-FLK (See note 2.) 10 E5AR-TQE3MB-FLK (See note 2.) E5AR-TCE3MB-FLK (See note 2.) E5AR-TQCE3MB-FLK 4 RS-485 E5AR-TQ43DW-FLK (See note 2.) E5AR-TC43DW-FLK (See note 2.) 8 8 RS-485 E5AR-TQQE3MWFLK E5AR-TCCE3MWWFLK E5AR-TQQE3MWWFLK (See note 2.) 4 10 (See note 3.) 4 8 None RS-485 E5AR-TPR4DF E5AR-TPRQE3MFFLK Model
96 x 96 Basic control Standard control mm (1 loop) Heating and cooling control
2 (pulse + pulse/cur- 4 rent) 2 (current + current) 2 (pulse + pulse/current) 2 (current + current) 2 (pulse + pulse/cur- 10 (See rent) note 3.) 2 (current + current) 4 (pulse + pulse/current + 2 current)
2 (pulse + pulse/cur- 4 2-loop control 2-loop standard control Single-loop heating and cooling control rent) Single-loop cascade control 2 (current + current) Single-loop control with remote SP Single-loop proportional control 4 (2 pulse + pulse/2 10 (See current) note 3.) 4-loop control 4-loop standard control 2-loop heating and cooling control (See note 4.) 4 (4 current) 4 (2 pulse + pulse/2 current) 10 (See note 3.)
Control valve Single-loop position-proportional control Relay outputs control (1 open, 1 closed) (1 loop) Relay outputs (1 open, 1 closed) and 1 current Note 1: 2: 3: 4:
Specify the power supply specifications when ordering. Model numbers for 100 to 240 VAC are different from those for 24 VAC/VDC. These models are for 100 to 240 VAC only. The outputs are transistor output. Only for coordinated operation. (A separate program cannot be set for each channel.)
Inspection Results
If an inspection report is required, it can be ordered at the same time as the Digital Controller using the following model number.
Accessories (Order Separately)
Terminal Cover
Descriptions Terminal Cover for E5AR Model E53-COV14
Inspection Report (Order Separately)
Model E5AR-K
Unit Label Sheet
Model Y92S-L1
Rubber Packing
Model Y92S-P4 Note: The Rubber Packing is provided with the Digital Controller.
2
E5AR-T
Specifications
Ratings
Supply voltage (See note 2.) Operating voltage range Power consumption Sensor input (See note 3.) CE marking UL certification 100 to 240 VAC, 50/60 Hz 100 to 120 VAC, 50/60 Hz 85% to 110% of rated supply voltage 22 VA max. (with maximum load) 15 VA/10 W max. (with maximum load) Thermocouple: K, J, T, E, L, U, N, R, S, B, W Platinum resistance thermometer: Pt100 Current input: 4 to 20 mA DC, 0 to 20 mA DC (including remote SP input) Voltage input: 1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC (including remote SP input) (Input impedance: 150 for current input, approx. 1 M for voltage input) 0 to 20 mA DC, 4 to 20 mA DC; load: 500 max. (including transfer output) (Resolution: Approx. 54,000 for 0 to 20 mA DC; Approx. 43,000 for 4 to 20 mA DC) Position-proportional control type (open, closed) N.O., 250 VAC, 1 A (including inrush current) Relay Output N.O., 250 VAC, 1 A (resistive load) Transistor Output Maximum load voltage: 30 VDC; Maximum load current: 50 mA; Residual voltage: 1.5 V max.; Leakage current: 0.4 mA max. 100 to 2.5 k Input ON: 1 k max.; OFF: 100 k min. Input ON: Residual voltage of 1.5 V max.; OFF: Leakage current of 0.1 mA max. Short-circuit: Approx. 4 mA Remote SP input Transfer output Control method Setting method Indication method Refer to the information on sensor input. Refer to the information on control output. 2-PID or ON/OFF control Digital setting using front panel keys or setting using serial communications 7-segment digital display and single-lighting indicator Character Height PV display: 12.8 mm; SV display: 7.7 mm; MV display: 7.7 mm Depends on model. -10 to 55C (with no icing or condensation) For 3 years of assured use: -10 to 50C (with no icing or condensation) 25% to 85% -25 to 65C (with no icing or condensation) Contact No-contact 24 VAC, 50/60 Hz; 24 VDC
Control output
Voltage (pulse) output 12 VDC, 40 mA max. with short-circuit protection circuit (E5AR-TQQE3MW-FLK: 21 mA max.) Current output Relay output
Auxiliary output
Potentiometer input Event input
Other functions Ambient operating temperature Ambient operating humidity Storage temperature
Note 1: Do not use an inverter output as the power supply. (Refer to Safety Precautions for All E5@R Models.) 2: The supply voltage (i.e., 100 to 240 VAC or 24 VAC/VDC) depends on the model. Be sure to specify the required type when ordering. 3: The Controller is equipped with multiple sensor input. Temperature input or analog input can be selected with the input type setting switch. There is basic insulation between power supply and input terminals, power supply and output terminals, and input and output terminals.
Input Ranges
Platinum Resistance Thermometer, Thermocouple, Current, or Voltage Input
Input type
Platinum resistance thermometer
Thermocouple
Current
Voltage
Name
2300 1800 1300 900 800 700 600 400 200 100 0 -100 -200
Pt100
K
J
T
E
L
U
N
R
S
B
( W/Re ) 5-26
2300.0
W
mA
V
1700.0 1300.0 850.0 850.0 850.0 1300.0
1700.0
1800.0
Temperature range (C)
500.0 400.0 150.00 400.0
600.0 400.0
20 to 4
100.0
10 to 20 to 5 to 1 5 to 0 0 0
0.0 -200.0 -150.00 -200.0 -20.0 -100.0 -20.0 -200.0 -100.0 -200.0 -200.0
0.0
0.0
0.0
Setting Minimum setting unit (SP and alarm) Input type setting switch
0 0.1C
1 0.01 C
2
3
4
5
6
7
8 0.1C
TC.PT
9
10
11
12
13
14
15
16
17
18
19
(Depends on scaling and number of decimal places.)
TC.PT
Set to TC.PT.
IN1 TYPE ANALOG
Set to ANALOG
IN1 TYPE ANALOG
Note: The shaded area indicates the setting status at the time of purchase.
3
E5AR-T
Characteristics
Indication accuracy Thermocouple input with cold junction compensation: (0.1% of PV or 1C, whichever is greater) 1 digit max. (See note 1.) Thermocouple input without cold junction compensation: (0.1% FS or 1C, whichever is smaller) 1 digit (See note 2.) Analog input: 0.1% FS 1 digit max. Platinum resistance thermometer input: (0.1% of PV or 0.5C, whichever is greater) 1 digit max. Position-proportional potentiometer input: 5% FS 1 digit max. Standard control (heating or cooling control), heating/cooling control, standard control with remote SP (2-input models only), heating/cooling control with remote SP (2-input models only), cascade standard control (2-input models only), cascade heating/cooling control (2-input models only), proportional control (2-input models only), position-proportional control (control-valve control models only)
Control mode
Influence of temperature Thermocouple input (R, S, B, W): (1% of PV or 10C, whichever is greater) 1 digit max. Other thermocouple input: (1% of PV or 4C, whichever is greater) 1 digit max. Influence of voltage *K thermocouple at -100C max.: 10C max. Platinum resistance thermometer: (1% of PV or 2C, whichever is greater) 1 digit max. Analog input: (1%FS) 1 digit max. Control period Proportional band (P) Integral time (I) Derivative time (D) Hysteresis Manual reset value Alarm setting range Input sampling period Insulation resistance Dielectric strength Vibration resistance (malfunction) Shock resistance (malfunction) Inrush current Weight Degree of protection Memory protection Applicable standards 0.2 to 99.0 s (in units of 0.1 s) for time-proportioning control output 0.00% to 999.99% FS (in units of 0.01% FS) 0.0 to 3,999.9 s (in units of 0.1 s) 0.0 to 3,999.9 s (in units of 0.1 s) 0.01% to 99.99% FS (in units of 0.01% FS) 0.0% to 100.0% (in units of 0.1% FS) -19,999 to 99,999 EU (See note 3.) (The decimal point position depends on the input type and the decimal point position setting.) 50 ms 20 M min. (at 500 VDC) 2,000 VAC, 50/60 Hz for 1 min (between charged terminals of different polarities) 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions 100 m/s2, 3 times each in X, Y, and Z directions 100 to 240-VAC models: 50 A max. 24 VAC/VDC models: 30 A max. Controller only: Approx. 450 g; Mounting bracket: Approx. 60 g; Terminal cover: Approx. 30 g Front panel: NEMA4X for indoor use; Rear case: IP20; Terminals: IP00 Non-volatile memory (number of writes: 100,000) UL 61010C-1, CSA C22.2 No. 1010-1 (Power supply voltage: 100 to 120 VAC): Pollution degree 2/Overvoltage category 2 EN 61010-1 (IEC 61010-1) (Power supply voltage: 100 to 240 VAC): Pollution degree 2/Overvoltage category 2 EMI: EN61326 Radiated Interference Electromagnetic Field Strength: EN55011 Group 1 Class A Noise Terminal Voltage: EN55011 Group 1 Class A EMS: EN61326 ESD Immunity: EN61000-4-2: 4 kV contact discharge (level 2) 8 kV air discharge (level 3) 10 V/m (amplitude-modulated, 80 MHz to 1 GHz, 1.4 GHz to 2 GHz) (level 3) EN61000-4-4:2 kV power line (level 3) 2 kV output line (relay output) (level 4) 1 kV measurement line, I/O signal line (level 4) 1 kV communications line (level 3) Conducted Disturbance Immunity: EN61000-4-6: 3 V (0.15 to 80 MHz) (level 3) Surge Immunity: EN61000-4-5:1 kV line to line (power line, output line (relay output)) (level 2) 2 kV line to ground (power line, output line (relay output)) (level 3) Power Frequency Magnetic Field Immunity: EN61000-4-8: 30 A/m (50 Hz) continuous field Voltage Dip/Interrupting Immunity: EN61000-4-11: 0.5 cycle, 100% (rated voltage) Electromagnetic Immunity: EN61000-4-3: Burst Noise Immunity:
EMC
Note 1: K-, T-, or N-type thermocouple at -100C max.: 2C 1 digit max. U- or L-type thermocouple: 2C 1 digit max. B-type thermocouple at 400C max.: No accuracy specification. R- or S-type thermocouple at 200C max.: 3C 1 digit max. W-type thermocouple: (0.3% of PV or 3C, whichever is greater) 1 digit max. 2: U- or L-type thermocouple: 1C 1 digit R- or S-type thermocouple at 200C max.: 1.5C 1 digit 3: "EU" (Engineering Unit) represents the unit after scaling. If a temperature sensor is used, it is either C or F.
4
E5AR-T
Communications Specifications
Transmission path connection Communications method Synchronization method Baud rate Transmission code Data bit length Stop bit length Error detection Multiple points RS-485 (two-wire, half duplex) Start-stop synchronization 9,600, 19,200, or 38,400 bps ASCII 7 or 8 bits 1 or 2 bits Vertical parity (none, even, odd) Block check character (BCC): CompoWay/F CRC-16: Modbus None RS-485 None 217 bytes
Flow control Interface Retry function Communications buffer
Communications response send wait time 0 to 99 ms, Default: 20 ms
Program Control Functions
Number of programs (patterns) Number of segments (steps) Maximum number of segments Segment setting method Segment times 32 (with 8 segments/program) 32 (with 8 programs) 256 Time setting (Segment set with set point and time.) Gradient setting (Segment set with set point, gradient, and time.) 0 h 0 min to 99 h 59 min 0 min 0 s to 99 min 59 s 0 min 00.0 s to 99 min 59.9 s 4 Set separately for each program. Select either stopping control or fixed SP operation. Select continuing, resetting, manual operation, run mode, or ramp back operation. Number of sets Setting method Alarm SP function Program status control Wait operation Segment operation Program operation Wait method Wait width setting Setting method Time signals Number of outputs Number of ON/OFF operations Setting method Segment outputs Number of outputs Setting method Program status output Program startup operation PV start Standby 8 Set separately for each program (automatic PID group selection also supported). Select from ramp SP and target SP. Advance, hold, and back Program repetitions and program links Select from waiting at segment ends and always waiting. Wait width upper limit and lower limit set separately for each program. ON/OFF setting for each segment 6 3 each per output Set separately for each program. 10 ON/OFF set for each segment. Program end output (pulse width can be set) Segment number output Select from segment 1 set point, slope-priority PV start, and time-priority PV start. Standby Select from resetting, continuing control at final set point, and fixed SP control. 10 max.
Alarm group num- Number of groups ber specifications Setting method Reset operation Startup operation PID sets
Operation end operation Number of event inputs
5
E5AR-T
Wiring Terminals
E5AR-T (Programmable Type)
E5AR-TQ4B
24 VAC/DC 100 to 240 VAC
E5AR-TC4B
A 1 2 3 4 5 6 1 2 3 4 5 6 FGHI
1
-
+ -
BCDE
COM SUB1 SUB2 COM SUB3 SUB4
Input power supply depends on model. 100 to 240 VAC or 24 VAC/DC (no polarity)
2 3 4 5 6
JK
Event input
EV1 EV2 + - I - + V COM - + TC
1 2 3 4 5 6 K
OUT2 Voltage output 12 V 40 mA
+ -
2 3 4
OUT1 + 5 Voltage output 12 V - 40 mA or 6 Current output 4 to 20 mA DC, 500 max. F 0 to 20 mA DC, 500 max. (Switched by output type setting.)
PT
(Thermocouple) (Current) (Voltage) (Resistance temperature input sensor)
E5AR-TQ43B-FLK
Auxiliary output (Relay output) 100 to 240 VAC
E5AR-TC43B-FLK
100 to 240 VAC
A 1 2 3 4
BCDE
!
B 1 2 3 4 5 6
COM SUB1 SUB2 COM SUB3 SUB4
OUT2 Voltage output 12 V 40 mA -
+ B(+) RS-485 - A(-) +
1 2 3 4
5 6 1 2 3 4 5 6 FGHI JK
OUT1 + 5 Voltage output 12 V 40 mA or - 6 Current output 4 to 20 mA DC, 500 max. F 0 to 20 mA DC, 500 max. (Switched by output type setting.)
Event input
EV1 EV2 + - - + V COM - + TC
1 2 3 4 5 6 K
OUT2 Current output
4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.) OUT1 Current output 4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
I
PT
(Thermocouple) (Current) (Voltage) (Resistance temperature input sensor)
Note
The power supply voltage must be 100 to 240 VAC or 24 VAC/DC for the E5AR-T to comply with CE marking requirements. The power supply voltage must be 100 to 120 VAC or 24 VAC/DC for the E5AR-T to comply with UL requirements.
+
!
B 1
-
Auxiliary output (Relay output)
24 VAC/DC
100 to 240 VAC
+ -
A 1 2 3 4 5 6 1 2 3 4 5 6
BCDE
!
Auxiliary output (Relay output)
B 1 2 3 4 5 6
COM SUB1 SUB2 COM SUB3 SUB4
+
Input power supply depends on model. 100 to 240 VAC or 24 VAC/DC (no polarity)
FGHI
OUT2 Current output 4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.) OUT1 Current output 4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
JK
Event input
1
+ - + -
EV1 EV2 + - I - + V COM - + TC
1 2 3 4 5 6 K
2 3 4 5 6 F
PT
(Thermocouple) (Current) (Voltage) (Resistance temperature input sensor)
A 1 2 3 4 5 6 1 2 3 4 5 6
BCDE
!
Auxiliary output (Relay output)
B 1 2 3 4 5 6
COM SUB1 SUB2 COM SUB3 SUB4
FGHI
B(+) RS-485 A(-)
JK
Event input
+
-
1 2 3 4 5 6 F
+
EV1 EV2 COM
-
+
1 2 3
-
+
+
-
+
-
4 5 6 K
-
I
V
PT
TC
(Thermocouple) (Current) (Voltage) (Resistance temperature input sensor)
6
E5AR-T
E5AR-TQE3MB-FLK
Auxiliary output (Transistor output)
E5AR-TCE3MB-FLK
Auxiliary output (Transistor output)
-
100 to 240 VAC
A 1 2 3 4 5 6 1 2 3 4 5 6
BCDE
COM
SUB1(B), SUB6(C) SUB2(B), SUB7(C)
BC 1 2 3 4 5 6 DE 1 2 3 4 5 6
OUT2 Current output 100 to 240 VAC
COM
- +
BC 1 2 3 4 5 6 DE 1 2 3 4 5 6
+ +
!
A 1 2 3 4 5 6 1 2 3 4 5 6
BCDE
SUB1(B), SUB6(C)
!
SUB2(B), SUB7(C) + SUB3(B), SUB8(C) + SUB4(B), SUB9(C) + SUB5(B), SUB10(C) +
Event input
SUB3(B), SUB8(C) + + SUB4(B), SUB9(C) SUB5(B), SUB10(C)+
Event input
EV3(E), EV7(D) EV4(E), EV8(D)
EV3(E),EV7(D) EV4(E),EV8(D) EV5(E),EV9(D)
FGHI
+ -
JK
EV5(E), EV9(D) EV6(E), EV10(D)
FGHI
JK
EV6(E),EV10(D)
COM
+ OUT2 Voltage output 12 V 40 mA -
B(+) RS-485 A(-)
1 2 3 4 5 6 F
+ -
I
COM
Event input
EV1 EV2 COM
1 2 3
- + TC
+ B(+) RS-485 - A(-) +
1 2
Event input
EV1 EV2
1 2 3
- + TC
OUT1 + Voltage output 12 V - 40 mA or Current output 4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
- + V
PT
4 5 6 K
(Thermocouple) (Current) (Voltage) (Resistance temperature input sensor)
4 to 20 mA DC, 500 max. 3 0 to 20 mA DC, 500 max. - 4 (Switched by output + type setting.) 5 OUT1 - Current output 6 4 to 20 mA DC, 500 max. F 0 to 20 mA DC, 500 max. (Switched by output type setting.)
+ -
I
COM
- +
V PT
4 5 6 K
(Thermocouple) (Current) (Voltage) (Resistance temperature input sensor)
E5AR-TQCE3MB-FLK
Auxiliary output (Transistor output) 24 VAC/DC + 100 to 240 VAC
A 1 2 3 4 5 6 1 2 3 4 5 6
BCDE
COM SUB1(B), SUB6(C)
BC 1 2 3 4 5 6 DE 1 2 3 4 5 6
Input power supply depends on model. 100 to 240 VAC or 24 VAC/DC (no polarity)
+ B(+) RS-485 - OUT2 A(-) + Voltage output 12 V 40 mA - OUT1 + Voltage output 12 V 40 mA or - Current output
4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
OUT4 Current output 4 to 20 mA DC, 500 max. + 0 to 20 mA DC, 500 max. (Switched by output - type setting.) + OUT3 Current output - 4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
+
!
+
SUB2(B), SUB7(C) + SUB3(B), SUB8(C) + + SUB4(B), SUB9(C) + SUB5(B), SUB10(C) Event input
1 2 3 4 5 6 F
EV3(E), EV7(D) EV4(E), EV8(D) EV5(E), EV9(D) EV6(E), EV10(D)
FGHI
JK
COM
1 2 3 4 5 6 G
+ - -
Event input EV1 EV2 COM - + TC
1 2 3 4 5 6 K
I
+ V
PT
(Thermocouple) (Current) (Voltage) (Resistance temperature input sensor)
Note
The power supply voltage must be 100 to 240 VAC or 24 VAC/DC for the E5AR-T to comply with CE marking requirements. The power supply voltage must be 100 to 120 VAC or 24 VAC/DC for the E5AR-T to comply with UL requirements.
7
E5AR-T
E5AR-TQ43DW-FLK (2-loop Control)
Auxiliary output (Relay output)
E5AR-TC43DW-FLK (2-loop Control)
Auxiliary output (Relay output)
100 to 240 VAC
A 1 2 3 4
BCDE
B 1 2 3 4 5 6
Event input
COM SUB1 SUB2 COM SUB3 SUB4
100 to 240 VAC
A 1 2 3 4
BCDE
B 1 2 3 4 5 6
Event input
COM
SUB1 SUB2
!
!
COM
SUB3 SUB4
B(+) RS-485 A(-)
+ -
1 2 3
5 6 1 2 3 4 5 6 FGHI JK
+ OUT2 Voltage output 12 V 40 mA -
E 1 2 3 4 5 6 1
+ B(+) 1 RS-485 - OUT2 A(-) 2 Current output +
5 6 1 2 3 4 5 6 FGHI JK
-
I
-
Input 2
+V - +
PT
+ TC
3
Input 1
Input 1
I
V
PT
(Thermocouple) (Current) (Voltage) (Resistance temperature input sensor)
(Thermocouple) (Current) (Voltage) (Resistance temperature input sensor)
E5AR-TQQE3MW-FLK (2-loop Control)
Auxiliary output (Transistor output) 24 VAC/DC + 100 to 240 VAC -
!
A 1 2 3 4 5 6 1 2 3 4 5 6
BCDE
COM
BC 1 2 3 4 5 6 DE 1 2 3 4 5 6
SUB1(B), SUB6(C) + SUB2(B), SUB7(C) + SUB3(B), SUB8(C) + SUB4(B), SUB9(C) + SUB5(B), SUB10(C) + Event input
- Input power supply depends on model. 100 to 240 VAC or 24 VAC/DC (no polarity)
+ B(+) RS-485 - OUT2 A(-) + Voltage output 12 V 40 mA - OUT1 + Voltage output 12 V 40 mA or Current output -
1 2 3 4 5 6 F
EV3(E), EV7(D) EV4(E), EV8(D)
FGHI
JK
EV5(E), EV9(D) EV6(E), EV10(D) COM
4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
1
OUT4 Voltage output 12 V 40 mA OUT3 Voltage output 12 V 40 mA or Current output + - + -
1
- + - + -
3 4 5 6 G
Input 2
Input 1
4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
(Thermocouple) (Current) (Voltage) (Resistance temperature input sensor)
Note
The power supply voltage must be 100 to 240 VAC or 24 VAC/DC for the E5AR-T to comply with CE marking requirements. The power supply voltage must be 100 to 120 VAC or 24 VAC/DC for the E5AR-T to comply with UL requirements.
-
-
2
2 3 4 5 6 K
I
V
PT
+ TC - + TC
I
V
PT
-
4 - 5 6 + TC K
+
Input 2
2
-
+
4 OUT1 + Voltage output 12 V 5 40 mA or - Current output 6 4 to 20 mA DC, 500 max. F 0 to 20 mA DC, 500 max. (Switched by output type setting.)
EV3 EV4 EV5 EV6 COM
3 4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. - 4 (Switched by output + type setting.) 5 - OUT1 6 Current output 4 to 20 mA DC, 500 max. F 0 to 20 mA DC, 500 max. (Switched by output type setting.)
E 1 2 3 4 5 6 1
EV3 EV4 EV5 EV6
COM
+
- -
+
+ +
-
I
-
V
2 3 4 5 6 K
+ - +
PT
+ - +
TC
I
V
PT
TC
+
-
8
E5AR-T
E5AR-TCCE3MWW-FLK (4-loop Control)
Auxiliary output (Transistor output) 24 VAC/DC 100 to 240 VAC + COM -
E5AR-TQQE3MWW-FLK (4-loop Control)
Auxiliary output (Transistor output)
BC 1 2 3 4 5 6
B(+) + -
!
1 2 3 4 5 6 1 2 3 4 5 6
A
BCDE
SUB1(B), SUB6(C) + SUB2(B), SUB7(C) + SUB3(B), SUB8(C) + + SUB4(B), SUB9(C) SUB5(B), SUB10(C) +
100 to 240 VAC
A 1 2 3 4 5 6 1 2 3 4 5 6
BCDE
- COM SUB1(B), SUB6(C) + SUB2(B), SUB7(C) SUB3(B), SUB8(C) SUB4(B), SUB9(C) + + +
BC 1 2 3 4 5 6 DE 1 2 3 4 5 6
1
- + - +
2 3 4 5 6 G
I
V
PT
+ TC
3 4 5 6
J, K
Input 1(K) Input 3(J)
- + TC
-
I
V
PT
4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
Input 1(K) Input 3(J)
(Thermocouple) (Current) (Voltage) (Resistance temperature input sensor)
(Thermocouple) (Current) (Voltage) (Resistance temperature input sensor)
E5AR-TPR4DF
Auxiliary output (Relay output) 24 VAC/DC + 100 to 240 VAC
E5AR-TPRQE3MF-FLK
A 1 2 3 4 5 6 1 2 3 4 5 6 FGHI
1 2 3 4 5 6 F
Relay output 250 VAC 1 A Closed
BCDE
-
2 3 4 5 6
Event input
SUB1 SUB2 COM SUB3 SUB4
Input power supply depends on model. 100 to 240 VAC or 24 VAC/DC (no polarity)
E 1 2 3 4 5 6
EV3 EV4 EV5 EV6
JK
COM
O W C
Potentiometer
2 OUT4 + Voltage output 12 V 3 40 mA - 4 OUT3 Voltage output 12 V + 5 40 mA or - Current output 6 4 to 20 mA DC, G 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
B(+) RS-485 A(-) + -
1 2 3 4 5 6 K
OUT2
Potentiometer
OUT2
+
OUT1
Open
- I
-
+
-
+ TC
V
PT
(Thermocouple) (Current) (Voltage) (Resistance temperature input sensor)
Note
The power supply voltage must be 100 to 240 VAC or 24 VAC/DC for the E5AR-T to comply with CE marking requirements. The power supply voltage must be 100 to 120 VAC or 24 VAC/DC for the E5AR-T to comply with UL requirements.
-
!
B 1
COM
24 VAC/DC + -
100 to 240 VAC
A 1 2 3 4 5 6 1 2 3 4 5 6
BCDE
!
Input power supply depends on model. 100 to 240 VAC or 24 VAC/DC (no polarity)
1
FGHI
1 2 3 4 5 6 F
Relay output 250 VAC 1 A Closed + - Open - + - +
OUT1
-
OUT3 Voltage output 12 V 21 mA or Current output
+
4 5 6 G
+
Input 2(K) Input 4(J)
+
-
-
+
OUT4 Current output 4 to 20 mA DC, 500 max. + 0 to 20 mA DC, 500 max. (Switched by output - type setting.) + OUT3 Current output - 4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
-
2
Voltage output 12 V 21 mA + -
2 3
Input 2(K) Input 4(J)
-
1
1
OUT4
+
+ B(+) 1 RS-485 - OUT2 A(-) 2 Current output + 4 to 20 mA DC, 500 max. 3 0 to 20 mA DC, 500 max. - (Switched by output 4 type setting.) + 5 OUT1 - Current output 6 4 to 20 mA DC, 500 max. F 0 to 20 mA DC, 500 max. (Switched by output type setting.)
+
+
-
!
- Input power supply depends on model. 100 to 240 VAC or 24 VAC/DC (no polarity)
SUB5(B), SUB10(C) + Event input
Event input
DE 1 2 3 4 5 6
OUT2
RS-485
1 2 3 4 5 6 F
A(-)
Voltage output 12 V 21 mA + OUT1 Voltage output 12 V 21 mA or Current output - + -
EV3(E), EV7(D) EV4(E), EV8(D) EV5(E), EV9(D)
EV3(E), EV7(D) EV4(E), EV8(D) EV5(E), EV9(D)
FGHI
JK
EV6(E), EV10(D) COM
4 to 20 mA DC, 500 max. 0 to 20 mA DC, 500 max. (Switched by output type setting.)
FGHI
JK
EV6(E), EV10(D) COM
-
I
1
-
V
2 3 4 5 6
J, K
+ - +
PT
+ TC - + TC
I
V
PT
Auxiliary output (Transistor output) - COM SUB1(B), SUB6(C) + SUB2(B), SUB7(C) + SUB3(B), SUB8(C) SUB4(B), SUB9(C) + +
BC 1 2 3 4 5 6 DE 1 2 3 4 5 6
-
+
SUB5(B), SUB10(C) + Event input
EV3(E), EV7(D) EV4(E), EV8(D) EV5(E), EV9(D) EV6(E), EV10(D) COM
JK
O W C
1 2 3 4 5 6 K
I
V
PT
TC
(Thermocouple) (Current) (Voltage) (Resistance temperature input sensor)
9
E5AR-T
Nomenclature
E5AR-T
Rear
Operation Indicators Channel Indicator
SUB1 SUB2 SUB3 SUB4 WAIT FSP
PV
Display No. 1
Bar Graph
SV
CMW MANU
Display No. 2
Program Status Indicators
PRG. SEG
RST RSP HOLD
Display No. 3
OUT1 OUT2 OUT3 OUT4 PF1 PF2
RUN/RST
Function Key 1/ Run/Reset Key
Function Key 2
Level Key
Mode Key
Down Key
Up Key
Dimensions
Note: All units are in millimeters unless otherwise indicated.
E5AR-T
11.5 96 3 2
110 95 91 x 91
SUB1 SUB2 SUB3 SUB4 WAIT
FSP
PV
SV
96
CMW
MANU
PRG. SEG
RST RSP HOLD
111
OUT1 OUT2 OUT3 OUT4 PF1 PF2
RUN/RST
Crimp terminal size: M3 Terminal cover (E53-COV14: order separately)
Panel Cutouts
920
+0.8
110 min.
920
+0.8
120 min.
* Recommended panel thickness is 1 to 8 mm. * Group mounting is not possible. (Maintain the specified mounting space between Controllers.) * When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications.
10
E5AR-T
Accessories (Order Separately)
Terminal Cover
E53-COV14 (for E5AR)
95
95
28.5
10.1
Unit Label Sheet
Y92S-L1
11.8
4.8
Rubber Packing
Y92S-P4 (for DIN96 x 96)
Order the Rubber Packing separately if it becomes lost or damaged. (Refer to page 2.) The Rubber Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the rubber packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in NEMA4. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider one year a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.) The Rubber Packing does not need to be attached if a waterproof structure is not required.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice.
11
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products: * Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog. * Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. * Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
2008.12 In the interest of product improvement, specifications are subject to change without notice.
Industrial Automation Company
http://www.ia.omron.com/
OMRON Corporation
(c)Copyright OMRON Corporation 2008 All Right Reserved.


▲Up To Search▲   

 
Price & Availability of E5AR-TQQE3MWFLK

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X